4.7 Earth-leakage Circuit Breaker
See Graphic: wc_gr000661
Generator models ending with an “AE” are equipped with an earth-
leakage circuit breaker. The circuit breaker is current-operated and
shuts off the power to the receptacles when a ground fault of 30 milli-
Amps or greater occurs in the generator or to a piece of equipment
attached to the generator. The circuit breaker is located on the control
panel and should be tested for proper operation every time the
generator is used.
To test the earth-leakage circuit breaker:
4.7.1 Start the generator.
4.7.2 Place main circuit breaker in closed position.
4.7.3 Push the TEST button (a) on the circuit breaker. The circuit breaker
lever will lower to the open position (b2). Power is now off at both
receptacles.
If the lever does not lower, the circuit breaker is not working. Do not
use the generator until the problem can be corrected.
4.7.4 To restore power to the receptacles, raise the circuit breaker lever to
the closed position (b1).
If the circuit breaker lever lowers to the open position during operation,
stop the generator and check it and equipment for defects. Repair all
defects before operating generator.